GD-3134D+GD-2134L UHV Cable Sheath?Fault?Locator
?
GD-3134D UHV cable sheath fault locator?
?Three fixed-point modes, suitable for different fault types.
- Step-voltage pinpointing mode:?indicate the fault point directly and quickly find the fault point.
- Fault current pinpointing mode:?Quickly find the fault point by measurement the resistance current?in the fault cable.
- HV rod pinpointing mode: Measure the DC voltage in the fault cable to find the fault point.
??High sensitivity and large response range.
?Adopting digital signal processing technology, the signal waveform is directly displayed, and the anti-interference ability is strong.
??Automatic zero adjustment to offset the influence of ground potential changes.
?Built-in large-capacity lithium-ion battery pack, automatic shutdown under voltage, and automatic shutdown after long-term no operation.
?Solid case, light weight and portable
GD-2134L UHV cable sheath fault signal generator
?Built-in high-voltage constant current source, the output voltage and current are continuously adjustable, allowing the output to operate in a long-term short circuit.
??It has multiple safety protection functions such as grounding lockout and high-voltage zero-position start.
?It can provide a signal source for the pinpointing of the fault on the sheath of the ultra-high voltage cable.
??The transmitter can be powered by mains electricity or a generator, and the sensor and receiver can be powered by dry batteries.
GD-3134D UHV cable sheath fault locator
Mode |
Accessory |
Accuracy |
Max. Sensitivity |
Max. Input Range |
Display |
Step-Voltage Pinpoint |
Step Voltage Probe |
1%(±0.1mV) |
0.1mV |
±300V |
Signal Waveform, Fault Point Direction |
Fault Current Pinpoint |
Current Sensor |
1%(±1mA) |
1mA |
±1A |
Signal Waveform, Fault Current Value |
HV Probe Rod Pinpoint |
Step Voltage Rod |
<1%(10V-10kV) |
1V(10-1kV) 10V(1kV-10kV) |
±10kV |
DC Voltage |
Others |
|||||
Built-in |
18650 Lithium Battery,?Standard 3.7V,?6.8Ah |
||||
Work Condition |
Temperature :-10℃-40℃;?Humidity 10-90%Rh;?Altitude <4500m |
||||
Dimension and Weight |
Dimension:?220mm×125mm×55mm;?Weight:?0.9kg. |
GD-2134L UHV cable sheath fault signal generator
Power supply |
AC 220V, can be connected to a generator (output power ≥ 1500W) |
Pinpoint Accuracy |
0.2m |
Output frequency |
1Hz |
Open circuit voltage |
Fundamental effective value 0~2800V,
(Pulsating DC, peak value 8kV, equivalent to the phase voltage peak value of 10kV line) |
Shirt circuit DC |
Effective value of fundamental wave 0~35mA
?(Pulsating DC, peak100mA) |
Work Condition |
Temperature: -10℃-40℃;?Humidity 10-90%Rh;?Altitude <4500m |
Max. Power |
900W |
Dimension and Weight |
Dimension:?417mmx234mmx318mm ?
Weight: 16.8kg |